SRT5000 Power Quality Analyzer
Features:
* Provide all the required power
quality information you need
* Four channel to measure current and voltage
* For all the voltage, current, power, electric power, harmonic
and phase for full analysis and diagnosis
* Can capture and record the power parameters and the waveform
at the same time
* Equip with three current clamp 008B, 040B, 068B, can deal with
all kinds of places
* Large LCD screen display, operation interface in both Chinese
and English
* USB interface connect with computer
¡¡
Accessories:
Host 1pc, Instrument knapsack 1pc,
Test Line 5pcs, Alligator clip 5pcs, Pin 5pcs, Charger 1pc, Disk
1pc, USB line 1pc, Lithium battery pack (in host ) 1pc, 2G
memory card (in host) 1pc.
Optional parts:
Current clamp SR008B 4pcs, Current
clamp SR040B 4pcs, Current clamp SR068B 4pcs
¡¡ |
¡¡
Function |
Function specification |
Test Function |
4 channel voltage and the 4 channel
current waveform real-time display |
True RMS of voltage and current |
DC component of Voltage
|
Peak value of current and voltage |
Minimum/maximum values over a period
of time of Current and voltage |
Phasor diagram
display |
Measurement of harmonic of each
phase, up to 50 harmonics |
Display harmonics ratio of current
and voltage of each phase |
The calculation of total harmonic
distortion (THD) |
Active/reactive/apparent power value
and gross of each phase |
Active/reactive/apparent electric
energy value and gross of each phase |
Calculation of transformer K factor |
Calculation of COS ¦Õ displacement
power factor (DPF) and power factor (PF) |
Calculation of flicker |
Calculation of three phase unbalance
|
Function of capture and monitoring |
Can monitoring instantaneous change
of power grid voltage current parameters, including
the voltage fluctuation and flicker, voltage surge,
sag and short supply interruption, temporary
overvoltage and harmonics. Instruments and can store
150 groups of transient waveform |
Function of starting current
monitoring |
Can monitor the startup current when
electrical equipment is starting, help to correctly
design capacity. It can display the trend curve of
effective value of starting current, the starting
current envelope curve, current voltage waveform of
the all eight channel. Monitoring for 100s, can
store each cycle of all waveform curve points within
100s. |
Function of storage |
Can totally record 123 parameters
such as the testing parameter of base testing
function (Urms,
Uthd,
Ucf,
Uunb,
Hz,
Vrms,
Vthd,
Vcf,
Vunb,
PST,
Arms,
Athd,
Acf,
Aunb,
KF,
W,
VAR,
VA,
PF,
Cos ¦Õ,
Tan ¦Õ),50 harmonics of voltage, 50
harmonic of current. Generate trend curve, the
interval time of recording is able to set, collect
once for 5s and can stored 75days. |
Alarm function |
Users can set up 40 groups alarm
monitoring project, each group can set different
judgments parameters (including 50 harmonics a total
of 123 different parameters), can be set different
alarm threshold, how long it will take to produce
the alarm when over the critical value is can be
set, etc. Can store up to a maximum of 12800 set
alarm record. |
Screenshots function |
In any test page screenshots can
store the current screen, automatically records the
time and test mode at the same time. Such as save
the current voltage wave, harmonic bar charts and
phasor diagram, etc. Screenshots can be saved up to
60 groups. |
Communication function |
Communicate with computer by USB
interface, monitoring software can display waveform
of power quality analysis, able to read those has
been detected and captured like transient waveform,
trend curve record, alarm list, test screenshots,
etc. |
Setting function |
The user can set the time and date,
set the display contrast ratio and brightness, set
each corresponding color of each phase line in the
instrument |
The connection mode of instruments
and the grid type can be set |
Can select different current clamp
and different voltage test strain ratio |
Can be selected menu in Chinese or
English menu |
Chinese/English help menu |
Each phase of the operation may at
any time by pressing "help" key for related
information |
¡¡
Accuracy of instruction
(under the base condition)
Measurement specification |
Range |
Display resolution |
The maximum error in the range of the
reference |
Frequency |
40Hz~70Hz |
0.01Hz |
¡À(0.01)Hz |
True RMS phase voltage |
0.0V~1000V |
Min resolution 0.1V |
¡À(0.5%+2dgt) |
True RMS line voltage |
0.0V~2000V |
Min resolution 0.1V |
¡À(0.5%+2dgt) |
DC Voltage |
0.0V~1000V |
Min resolution 0.1V |
¡À(0.5%+5dgt) |
True RMS current |
0.0mA~1000A |
Min resolution 0.1mA |
¡À(0.5%+2dgt) |
Phase voltage peak |
0.0V~1414V |
Min resolution 0.1V |
¡À(0.5%+5dgt) |
Line voltage peak |
0.0V¡«2828V |
Min resolution 0.1V |
¡À(0.5%+5dgt) |
Current peak |
0.0mA~1414A |
Min resolution 0.1mA |
¡À(0.5%+2dgt) |
Peak factor |
1.00~3.99 |
0.01 |
¡À(1%+2dgt) |
4.00~9.99 |
0.01 |
¡À(5%+2dgt) |
Active power |
0.000W~9999.9KW |
Min resolution 0.001W |
¡À(1%+2dgt);Cos¦Õ¡Ý0.8 |
¡À(1.5%+10dgt);0.2¡ÜCos¦Õ<0.8 |
Reactive power Inductive & Capacitive |
0.000VAR~9999.9KVAR |
Min resolution 0.001VAR |
¡À(1%+2dgt);Sin¦Õ¡Ý0.5 |
¡À(1.5%+10dgt);0.2¡ÜSin¦Õ<0.5 |
Apparent power |
0.000VA~9999.9KVA |
Min resolution 0.001VA |
¡À (1 %) |
Power factor |
-1.000~1.000 |
0.001 |
¡À(1.5%+2dgt);Cos¦Õ¡Ý0.5 |
¡À(1.5%+10dgt);0.2¡ÜCos¦Õ<0.5 |
Active energy |
0.000Wh~9999.9MWh |
Min resolution 0.001Wh |
¡À(1%+2dgt);Cos¦Õ¡Ý0.8 |
¡À(1.5%+10dgt);0.2¡ÜCos¦Õ<0.8 |
Reactive energy
Inductive & Capacitive |
0.000VARh~9999.9MVARh |
Min resolution 0.001VARh |
¡À(1%+2dgt);Sin¦Õ¡Ý0.5 |
¡À(1.5%+10dgt);0.2¡ÜSin¦Õ<0.5 |
Apparent power |
0.000Vah~9999.9MVAh |
Min resolution 0.001VAh |
¡À (1%) |
Phase angle |
-179¡ã~180¡ã |
1¡ã |
¡À(1¡ã) |
Tan ¦Õ(VA¡Ý50VA) |
-57.289~57.289 |
Min resolution 0.001 |
¡À(1%+5dgt) |
The displacement power factor (DPF) |
-1.000~1.000 |
0.001 |
¡À(1%+5dgt) |
Harmonic ratio (Vrms>50V) |
0.0 %~99.9 % |
0.1 % |
¡À(1%+5dgt) |
Harmonic Angle (Vrms>50V) |
-179¡ã~180¡ã |
1¡ã |
¡À(3¡ã)harmonic1~25 |
¡À(10¡ã)harmonic26~50 |
Rate of total harmonic (DF or THD-F)¡Ü50 |
0.0 %~99.9 % |
0.1 % |
¡À(1%+5dgt) |
Distortion factor (DF or THD-R)¡Ü50 |
0.0 %~99.9 % |
0.1 % |
¡À(1%+10dgt) |
Transformer K factor |
1.00~99.99 |
0.01 |
¡À (5 %) |
Three-phase imbalance |
0.0%~100 % |
0.1 % |
¡À (1 %) |
¡¡
Feature of current clamp
(Optional)
Model |
Current clamp |
True RMS current |
Max error True RMS current |
Max error of Phase Angle ¦µ |
SR008B
§¶8mm |
|
0.0Ma~100mA |
¡À(1 % + 3dgt) |
¡À(1.5¡ã),Arms¡Ý20mA |
100mA~10.0A |
¡À(1 % + 3dgt) |
¡À(1¡ã) |
SR040B
§¶40mm |
|
0mA~999mA |
¡À(1 % + 3dgt) |
¡À(1.5¡ã),Arms¡Ý100mA |
1.00A~300A |
¡À(1 % + 3dgt) |
¡À(1¡ã) |
SR068B §¶68mm |
|
0.00A~10A |
¡À(2 % + 3dgt) |
¡À(1.5¡ã) ,Arms¡Ý1.00A |
10A~100A |
¡À(2 % + 3dgt) |
¡À(1¡ã) |
100A~1000A |
¡À(2 % + 3dgt) |
¡À(1¡ã) |
¡¡
General specification
Power supply |
Rechargeable lithium-ion battery pack
9.6V,
backup charger |
Battery indicator |
Battery symbol"
" shows dump energy, When the voltage is too low,
automatic shutdown after the 1 minute |
Power consumption |
Current consumption of normal test
430mA, continuous working for 8 hours |
Display mode |
LCD color screen, 640dots*480dots,
5.6 inches, display demo: 116mm*88mm |
Instrument dimensions |
L*W*T: 240mm*170mm*68 mm |
Size of clamp |
SR008B current clamp:
7.5mm*13mm; SR040B current clamp:
35mm*40mm; SR068B current clamp: 68mm*68mm |
Number of channels |
4U/4I |
Line voltage |
1.0V~2000V |
Phase voltage |
1.0V~1000V |
Current |
SR008B current clamp 0.0mA~10.0A;
SR040B current clamp 0mA~300A; SR068B current
clamp 0.00A~1000A |
Frequency |
40Hz~70Hz |
Parameters of electricity |
W, VA, var, PF, DPF, cos ¦Õ, tan ¦Õ |
power parameter |
Wh, varh, Vah |
Harmonic |
0~50times |
Total harmonic distortion |
0~50 times, each phase |
Model |
Waveform model, harmonic model, Power
and power energy mode, Waveform capture mode, Trend
chart pattern, alarm mode, Screen mode |
Set number of Transient record |
150sets |
Record |
300 days (all the parameter, recode
one point every 5 seconds) |
Min/Max records |
Can be measured maximum minimum value
over a period of time |
Warning |
40 different types of parameter
selection,12800set warning record |
Phasor diagram display |
Automatically |
Capacity of screenshots |
60 |
Language of manual |
Chinese and English |
Communication |
USB |
Automatically shutdown |
At alarm/trend chart
records/transient capture mode (pending or ongoing),
5 minutes without keystrokes, monitoring instruments
automatically into low power mode, press any key to
activate. |
In other test mode, 15 minutes
without keystrokes, prompt automatic shutdown after
1 minute |
Quality of the instrument |
7.8Kg(with package) |
length of test line |
3m; length Current clamp wire:2m |
Working temperature |
-10¡ãC~40¡ãC;
below 80%Rh |
Input impedance |
Input impedance for the test voltage:
2M¦¸ |
Withstand voltage |
Can withstand1000 V / 50Hz sinusoidal
AC voltage for 1 minute between Instrument wiring
and the shell |
Insulation |
Between instrument wiring and
shell¡Ý100M¦¸ |
Safety rules |
IEC 61010 1000V Cat III / 600V CAT
IV, IEC61010-031, IEC61326, pollusion 2 |
|